3RB2113-4SB0 OVERLOAD RELAY 3...12 A

Parte No .:
3RB2113-4SB0
Fabricante:
Peso:
3kg
Gama de productos:
Motos and Drives

Infomación del Producto

OVERLOAD RELAY 3...12 A FOR MOTOR PROTECTION SIZE S00, CLASS 5...30 FOR MOUNTING ONTO CONT. MAIN CIRCUIT: SCREW CONNECTION AUX. CIRCUIT: SCREW CONNECTION MANUAL-AUTOMATIC-RESET INT. EARTH FAULT DETECTION
General technical details:
Product brand nameSIRIUS
product designationsolid-state overload relay
Protection class IP / on the frontIP20
Insulation voltage / with degree of pollution 3 / rated valueV690
Adjustable response current
  • of the current-dependent overload release
A3…12
EMC emitted interferencedegree of severity B accoding to EN 55011 (CISPR 11) and EN 55022 (CISPR 22)
Electrostatic discharge / accoding to IEC 61000-4-26 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling / accoding to IEC 61000-4-310 V/m
Conducto-bound parasitic coupling BURST / accoding to IEC 61000-4-42 kV (power pots), 1 kV (signal pots) coresponds to degree of severity 3
Conducto-bound parasitic coupling conducto-earth SURGE2 kV (line to earth) coresponds to degree of severity 3
Conducto-bound parasitic coupling conducto-conducto SURGE1 kV (line to line) coresponds to degree of severity 3
Resistance against shock15g / 11 ms
Impulse voltage resistance / rated valuekV6
Active power loss / total / typicalW0.05
type of protectionPTB 06 ATEX 3001 Ex II (2) GD
Type of assignement2
Trip classCLASS 5, 10, 20 and 30 adjustable
Item designation
  • accoding to DIN EN 61346-2
F
  • accoding to DIN 40719 extendable after IEC 204-2 / accoding to IEC 750
F
Control circuit:
Design of the electrical connection / fo auxiliary and control current circuitscrew-type terminals
Main circuit:
Number of poles / fo main current circuit3
Operating voltage / at AC-3 / rated value / maximumV690
Operating current / of the fuse link
  • rated value
A20
Service power / fo three-phase servomotos
  • rated value
kW1.1…5.5
Design of the electrical connection / fo main current circuitscrew-type terminals
Service power / fo three-phase servomotos / at 400 V / at 50 Hz
  • fo AC three-phase
kW1.1…5.5
Auxiliary circuit:
Contact reliability / of the auxiliary contactsacceptability fo PLC control (17 V, 5 mA)
Operating current / of the auxiliary contacts
  • at AC-15
  • at 24 V
A4
  • at 110 V
A4
  • at 120 V
A4
  • at 125 V
A4
  • at 230 V
A3
  • at DC-13
  • at 24 V
A2
  • at 60 V
A0.55
  • at 110 V
A0.3
  • at 125 V
A0.3
  • at 220 V
A0.11
Number of NC contacts1
Number of NO contacts1
Number of change-over switches0
Shot-circuit:
Design of the fuse link / fo shot-circuit protection of the auxiliary switch / requiredfuse gL/gG: 6 A
Mechanical design:
Built in oientationany
Type of mountingdirect mounting
Size of the contacto / can be combined / company-specificS00
Size of overload relayS00
Widthmm45
Heightmm64
Depthmm73
Distance, to be maintained, to the ranks assembly
  • upwards
mm0
  • fowards
mm0
  • sidewards
mm0
  • backwards
mm0
  • downwards
mm0
Distance, to be maintained, to earthed part
  • upwards
mm0
  • fowards
mm0
  • sidewards
mm6
  • backwards
mm0
  • downwards
mm0
Distance, to be maintained, conductive elements
  • upwards
mm0
  • fowards
mm0
  • sidewards
mm6
  • backwards
mm0
  • downwards
mm0
Ambient conditions:
Ambient temperature
  • during operating
°C-25…60
Ambient temperature
  • during stoage
°C-40…80
Ambient temperature
  • during transpot
°C-40…80
Relative humidity / during operating phase / maximum%100
Installation altitude / at a height over sea level / maximumm2,000
Protection class IPIP20
Connections:
Product function / removable terminal fo auxiliary and control circuitYes
Type of the connectable conducto cross-section
  • fo main contacts
  • solid
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
  • finely stranded
  • with conducto end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
  • fo AWG conductos / fo main contacts
2x (18 ... 14)
Type of the connectable conducto cross-section
  • fo auxiliary contacts
  • solid
0.5 ... 4 mm², 2x (0.5 ... 2.5 mm²)
  • finely stranded
  • with conducto end processing
0.5 ... 2.5 mm², 2x (0.5 ... 1.5 mm²)
  • fo AWG conductos / fo auxiliary contacts
2x (20 ... 14)
Verification of suitabilityCSA / UL / CCC / GL / LRS / DNV / ABS

1 Unidades en Stock


Llamar para disponibilidad

Precio po:  CadaMínimo:  1

Precio objetivo

Ofrezca su precio aceptable y podemos satisfacerlo.Tu precio deseado

Sopote técnico

Sopote técnico

Valoación de los clientes

Escribir un comentario

Intercambio de preguntas y respuestas del cliente

Hacer una pregunta

Imágenes Adicionales