AS-INTERFACE POWER SUPPLY IP20; OUT: AS-I DC30V, 3A IN: AC 120V/230V W. INTEGR. GROUND FAULT DETECTION W. INTEGR. OVERLOAD DETECTION |
General technical data: |
Type of device | | AS-Interface power supply unit IP20 |
version | | single output |
input voltage / nominal value / AC | | |
| V | 120 |
| V | 230 |
Additional function | | integrated ground-fault detection, remote reset and remote indication |
Inputs: |
input | | single phase AC |
| | |
| V | 85…132 |
| V | 176…253 |
- Mains buffering time / at Ia rated / min
| | 20 |
| | 50/60 Hz |
| Hz | 47…63 |
| | changeover switch |
| | T 3.15 (not accessible) |
- recommended circuit breaker / (IEC 898) / in the main supply line
| | 6 A, characteristic C |
Connections / input | | spring-loaded terminal connection input (0.2 ... 2.5 mm2)/ diagnosis (0.14 ... 1.5 mm2) |
Outputs: |
output | | |
- DC-voltage / controlled floating / according to AS-Interface spezification
| | yes |
- voltage rated value / Ua rated / DC
| | 30 V |
| | |
| V | 29.5…31.6 |
| | 3 A |
- residual ripple / peak-to-peak / ( 0-10 kHz, AS-i+/AS-i- ) / max
| mV | 300 |
- spikes / peak-to-peak / ( 10-500 kHz, AS-i+/AS-i- ) / max
| mV | 50 |
Connections / Output | | spring-loaded terminal connection output (0.2 ... 2.5 mm2)/ diagnosis (0.14 ... 1.5 mm2) |
Efficiency / heat loss: |
Efficiency / at Ua rated, Ia rated | % | 84 |
Protective and monitoring functions |
Output overvoltage protection | | yes (< 35V) |
Current limitation / from min. | | 3.5 A |
Short-circuit protection | | yes |
protection class / ( EN 60 950/IEC 950 ) | | I |
licence | | CE, UL, CSA (available soon) |
Electrical isolation / primary/secondary | | SELV according to EN 60 950 and EN 50 178 |
Protection class IP | | IP20 |
EMC: |
electromagnetic compatibility (EMC) | | |
| | EN 61 000-6-2, EN 61 000-4-2/-3/-4/-5/-11 |
| | class B according to EN 55 022, IEC 61 000-6-3 |
Ambient conditions: |
Ambient temperature | | |
| °C | 70…-10 |
| °C | 80…-25 |
humidity rating | | climatic class DIN 50010, relative humidity max. 100% without condensation |
Type of mounting | | fixing on standard mounting rail DIN EN 59 022-35 x 7.5 mm snap-on |
Width | mm | 50 |
Height | mm | 125 |
Depth | mm | 125 |