Your cart is empty

3RV1041-4KA10 CIRCUIT-BREAKER SIZE S3

Part No.:
3RV1041-4KA10
Manufacturer:
Weight:
0.45kg
Product Range:
Industrial Controls

Product Information

CIRCUIT-BREAKER SIZE S3, FOR MOTOR PROTECTION, CLASS 10, A-REL. 57...75A, N-REL. 975A, SCREW TERMINAL, STANDARD SWITCHING CAPACITY
General technical data:
Product brand nameSIRIUS
product designationcircuit breaker
Size of the circuit-breakerS3
Trip classCLASS 10
Degree of pollution3
Installation altitude / at a height over sea level / maximumm2,000
Protection class IP / on the frontIP20
Ambient temperature
  • during storage
°C-50…80
  • during operating
°C-20…70
  • during transport
°C80…-50
Resistance against shock25g / 11 ms
Insulation voltage / rated valueV690
Impulse voltage resistance / rated valueV6,000
Active power loss / total / typicalW30
Item designation
  • according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
Q
  • according to DIN EN 61346-2
Q
Mechanical operating cycles as operating time / of the main contacts / typical50,000
Type of the driving mechanism / motor driveNo
Design of the operating mechanismselector switch
Product function
  • overload protection
Yes
  • phase disturbance recognition
Yes
Product component
  • auxiliary switch
No
  • undervoltage release mechanism
No
  • trip indicator
No
Product extension / optional / motor driveYes
Main circuit:
Number of poles / for main current circuit3
type of voltageAC/DC
Operating voltage / at AC-3 / rated value / maximumV690
Operating current / at AC-3 / at 400 V / rated valueA75
Service power / at AC-3
  • at 400 V / rated value
kW37
Frequency of operation / at AC-3 / according to IEC 60947-6-2 / maximum1/h15
Arrangement of electrical connectors / for main current circuitfront side
Adjustable response current
  • of the non-delayed short-circuit release
A975…975
Adjustable response current
  • of the current-dependent overload release
A57…75
Continuous current / rated valueA75
Product extension / auxiliary switchYes
Auxiliary circuit:
Number of NC contacts / for auxiliary contacts / instantaneous switching0
Number of NO contacts / for auxiliary contacts / instantaneous switching0
Number of change-over switches / for auxiliary contacts0
Inputs/ Outputs:
Number of digital inputs0
Short-circuit:
Breaking capacity limit short-circuit current (lcu)
  • at 400 V / rated value
kA50
  • at 500 V / rated value
kA8
  • at 690 V / rated value
kA5
Design of the electrical connection / for auxiliary and control current circuitscrew-type terminals
Design of the overcurrent release and short-circuit releasethermomagnetic
Installation/mounting/dimensions:
Built in orientationany
Type of mountingscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022
Widthmm70
Heightmm165
Depthmm174
Distance, to be maintained, to the ranks assembly
  • backwards
mm0
  • sidewards
mm0
Product function / removable terminal for auxiliary and control circuitNo
Connections:
Design of the electrical connection
  • for main current circuit
screw-type terminals with box terminals
Type of the connectable conductor cross-section
  • for main contacts
  • solid
2x (2.5 ... 16 mm²)
  • stranded
2x (10 ... 50 mm²), 10 ... 70 mm²
  • finely stranded
  • with conductor end processing
2x (2.5 ... 35 mm²), 2.5 ... 50 mm²
Conductor cross section that can be connected / for main contacts
  • solid
mm²2.5…16
  • stranded
mm²10…70
  • stranded wire
  • with conductor end processing
mm²2.5…50

1 Units in Stock


Call for Availability

Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question