General technical details: |
Product brand name | | SIRIUS |
product designation | | safety relays |
Design of the product | | for EMERGENCY-STOP units |
protection class IP / of the housing | | IP20 |
Protection class IP / of the terminal | | IP20 |
|
Insulation voltage / rated value | V | 300 |
Ambient temperature | | |
| °C | -40…80 |
| °C | -25…60 |
Air pressure | | |
| kPa | 90…106 |
Relative humidity | | |
| % | 10…95 |
Installation altitude / at a height over sea level / maximum | m | 2,000 |
Resistance against vibration / according to IEC 60068-2-6 | | 5 ... 500 Hz: 0,075 mm |
Resistance against shock | | 8g / 10 ms |
Impulse voltage resistance / rated value | V | 4,000 |
EMC emitted interference | | EN 60947-5-1 |
Item designation | | |
- according to DIN 40719 extendable after IEC 204-2 / according to IEC 750
| | KT |
- according to DIN EN 61346-2
| | F |
Number of sensor inputs | | |
| | 1 |
Design of the cascading | | none |
Type of the safety-related wiring / of the inputs | | single-channel and two-channel |
Product feature / transverse contact-secure | | Yes |
safety Integrated Level / according to IEC 61508 | | SIL3 |
SIL claim limit (for a subsystem) / according to EN 62061 | | 3 |
Performance level (PL) / according to ISO 13849-1 | | e |
Category / according to EN 954-1 | | 4 |
Category / according to ISO 13849-1 | | 4 |
Probability of dangerous failure per hour (PFHD) / with high demand rate / according to EN 62061 | 1/h | 0.2700000000000001E-8 |
Average probability of failure on demand (PFDavg) / with low demand rate / according to IEC 61508 | 1/h | 0.24E-5 |
T1 value / for proof test interval or service life / according to IEC 61508 | a | 20 |
Number of outputs / as contact-affected switching element | | |
- as NC contact / for reporting function / instantaneous switching
| | 1 |
- as NO contact / safety-related / instantaneous switching
| | 2 |
- as NO contact / safety-related/ delayed switching
| | 2 |
Number of outputs / as contact-less semiconductor switching element | | |
| | |
| | 0 |
| | 0 |
| | |
| | 0 |
| | 0 |
Stop category / according to DIN EN 60204-1 | | 0 + 1 |
General technical details: | | |
Design of the input | | |
- cascading-entrance/operation-even switching
| | No |
| | Yes |
| | Yes |
Design of the electrical connection / jumper socket | | Yes |
Operating cycles / maximum | 1/h | 1,000 |
Switching capacity current / of the NO contacts of the relay outputs | | |
| | |
| A | 5 |
| A | 0.2 |
| A | 0.1 |
| | |
| A | 5 |
| A | 5 |
Switching capacity current / of the NC contacts of the relay outputs | | |
| | |
| A | 5 |
| A | 0.2 |
| A | 0.1 |
| | |
| A | 5 |
| A | 5 |
Thermal current / of the contact-affected switching element / maximum | A | 5 |
Electrical operating cycles as operating time / typical | | 100,000 |
Mechanical operating cycles as operating time / typical | | 10,000,000 |
Design of the fuse link / for short-circuit protection of the NO contacts of the relay outputs / required | | gL/gG: 6 A, or quick: 10 A |
Resistance to direct current / of the cable / maximum | Ω | 30 |
Cable length / between sensor and electronic evaluation device / with Cu 1.5 mm² and 150 nF/km / maximum | m | 1,000 |
Make time / with automatic start | | |
| ms | 80 |
Backslide delay time / at mains power cut | | |
| ms | 100 |
Adjustable backslide delay time | | |
- after opening of the safety circuits
| s | 0.05…3 |
Recovery time / after mains power cut / typical | s | 1 |
Pulse duration | | |
- of the sensor input / minimum
| ms | 25 |
- of the ON pushbutton input / minimum
| s | 0.025 |
Control circuit: | | |
Type of voltage / of the controlled supply voltage | | DC |
Control supply voltage / 1 / for DC / rated value | V | 24 |
Working range factor supply voltage rated value / of the magnet coil | | |
| | |
| | 0.85…1.1 |
| | |
| | 0.85…1.1 |
| | 0.85…1.1 |
Installation/mounting/dimensions: | | |
Built in orientation | | any |
Type of mounting | | screw and snap-on mounting |
Width | mm | 44.8 |
Height | mm | 138.5 |
Depth | mm | 120 |
Connections: | | |
Design of the electrical connection | | screw-type terminals |
Type of the connectable conductor cross-section | | |
| | 1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²) |
| | |
| | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
Type of the connectable conductor cross-section / for AWG conductors | | |
| | 2x (24 ... 16) |
| | 2x (24 ... 16) |
Product Function: |
Product function | | |
| | No |
| | No |
- protective door monitoring
| | Yes |
| | Yes |
- magnetic switch monitoring Normally closed contact-Normally open contact
| | No |
- rotation speed monitoring
| | No |
| | No |
| | No |
| | No |
- magnetic switch monitoring Normally closed contact-Normally closed contact
| | No |
| | No |
| | Yes |
Suitability for interaction / pressing control | | No |
Acceptability for application | | |
| | Yes |
- position switch monitoring
| | Yes |
- EMERGENCY-OFF circuit monitoring
| | Yes |
- opto-electronical protection device monitoring
| | No |
- magnetically operated switches monitoring
| | No |
- proximity switches monitoring
| | No |
| | Yes |
Verification of suitability | | BG, SUVA, UL, CSA, EN 60204-1, EN ISO 12100, EN 954-1, IEC 61508 |
- TÜV (German technical inspectorate) certificate
| | Yes |
| | Yes |
| | Yes |