Your cart is empty

6AG1135-4GB01-2AB0 SIPLUS ET200S EM 2AO I STANDARD

Manufacturer:
Weight:
0.04kg
Product Range:
Converters

Product Information

SIPLUS ET200S EM 2AO I STANDARD -25 ... +70 DGR C WITH CONFORMAL COATING BASED ON 6ES7135-4GB01-0AB0 . +/-20MA; 13 BIT + VZ, 4 . .20MA; 13 BIT CYCLE TIME < 1MS WITH LED GF (GROUP FAULT)
Supply voltage
Load voltage L+
Rated value (DC)24 V; From power module
Reverse polarity protectionYes
Input current
from load voltage L+ (without load), max.150 mA
from backplane bus 3.3 V DC, max.10 mA
Power losses
Power loss, max.2 W
Address area
Address space per module
Address space per module, max.4 byte
Analog outputs
Number of analog outputs2
Current output, no-load voltage, max.18 V
Cycle time (all channels) max.1.5 ms
Output ranges, current
-20 to +20 mAYes
4 to 20 mAYes
Connection of actuators
for current output 2-conductor connectionYes
for current output 4-conductor connectionNo
Load impedance (in rated range of output)
with current outputs, max.500 Ω
with current outputs, inductive load, max.1 mH
Destruction limits against externally applied voltages and currents
Voltages at the outputs towards MANA15 V; max. 15 V continuous; 75 V for max. 1 s (mark to space ratio 1:20)
Current, max.50 mA; DC
[nicht versorgt: TAK_ABT299_001_000]
Cable length, shielded, max.200 m
Analog value creation
Integrations and conversion time/ resolution per channel
Resolution with overrange (bit including sign), max.14 bit; 4 to 20 mA: 13 bits, +/-20 mA: 14 bits
Settling time
for resistive load0.1 ms
for capacitive load0.5 ms
for inductive load0.5 ms
Errors/accuracies
Output ripple (based on output area, bandwidth 0 to 50 kHz)+/- 0,02 %
Linearity error (relative to output area)+/- 0,02 %
Temperature error (relative to output area)+/- 0,01 %/K
Repeat accuracy in settled status at 25 °C (relative to output area)+/- 0,05 %
Operational limit in overall temperature range
Current, relative to output area+/- 0,5 %
Basic error limit (operational limit at 25 °C)
Current, relative to output area+/- 0,3 %
Interrupts/diagnostics/status information
Substitute values connectableYes; 0 to 65535 (range of values must be within the rated range)
Diagnoses
Wire breakYes
Group errorYes
Diagnostics indication LED
Group error SF (red)Yes
Parameter
Remark7 bytes
Output type/rangedeactivated / +/-20 mA / 4 to 20 mA
Diagnosis: wire breakDisable / enable
Group diagnosticsDisable / enable
Behavior on CPU/Master STOPOutput current and de-energized/substitute a value/keep last value
Ex(i) characteristics
Max. values of output circuits (per channel)
Uo (output no-load voltage), max.18 V
Galvanic isolation
Galvanic isolation analog outputs
between the channelsNo
between the channels and the backplane busYes
between the channels and the load voltage L+Yes
Permissible potential difference
between MANA and M internally (UISO)75 VDC / 60 VAC
Ambient conditions
Extended ambient conditions
Relative humidity
with condensation / maximum100 %
Resistance
to biologically active substances / conformity with EN 60721-3-3Yes
to chemically active substances / conformity with EN 60721-3-3Yes
to mechanically active substances / conformity with EN 60721-3-3Yes
Dimensions
Width15 mm
Height81 mm
Depth52 mm
Weight
Weight, approx.40 g

1 Units in Stock


Call for Availability

Price for:  EachMinimum:  1

Target Price

Offer your acceptable price, and we may make you satisfied.Your Target Price

Technical Support

Technical Support

Customer Reviews

Write Review

Customer Q&A Exchange

Ask A Question