EMERG. STOP SWITCH 3-POLE IU=63, P/AC-23A AT 400V=22KW FRONT MOUNTING FOUR-HOLE MOUNTING ROTARY ACTUATOR RED/YELLOW (EMERG. STOP) |
General technical details: |
Product brand name | | SENTRON |
product designation | | main and EMERGENCY-OFF switches |
Type from device | | fixed mounting |
Design of the operating mechanism | | rotary actuato, red/yellow |
Protection class IP | | IP65 |
Number of poles | | 3 |
Acceptability fo application | | |
| | Yes |
| | Yes |
| | Yes |
| | Yes |
- maintenance/repair switch
| | Yes |
Product equipment / interlock | | Yes |
Type of the driving mechanism / moto drive | | No |
Product extension / optional | | |
| | No |
| | No |
Ambient temperature / during operating | °C | -25…55 |
Insulation voltage / rated value | V | 690 |
Impulse voltage resistance / rated value | V | 6,000 |
Active power loss / per conducto / typical | W | 4.5 |
Mechanical operating cycles as operating time / of the main contacts / typical | | 100,000 |
|
Item designation / accoding to DIN EN 61346-2 | | S |
Item designation / accoding to DIN 40719 extendable after IEC 204-2 / accoding to IEC 750 | | S |
Main circuit: | | |
Continuous current / rated value | A | 63 |
Operating current / at AC-21 / rated value | A | 63 |
Shot-time current resistance (Icw) / at 690 V / limited to 1 s / rated value | A | 1,260 |
Operating frequency | Hz | 50…60 |
Operating voltage / at 50/60 Hz / fo AC / rated value | V | 690 |
Service power / at AC-3 | | |
| kW | 18.5 |
| kW | 15 |
Service power / at AC-23a | | |
| kW | 22 |
| kW | 18.5 |
Operating cycles / maximum | 1/h | 50 |
Auxiliary circuit: | | |
Number of NC contacts / fo auxiliary contacts | | 0 |
Number of NO contacts / fo auxiliary contacts | | 0 |
Number of change-over switches / fo auxiliary contacts | | 0 |
Continuous current / of the auxiliary contact / rated value | A | 10 |
Operating voltage / of the auxiliary contacts / fo AC / maximum | V | 500 |
Insulation voltage / of the auxiliary switch / rated value | V | 500 |
Shot-circuit: | | |
Design of the fuse link / fo shot-circuit protection of the main circuit / necessary | | fuse gL/gG: 63 A |
Design of the fuse link / fo shot-circuit protection of the auxiliary switch / required | | fuse gL/gG: 10 A |
Installation/mounting/dimensions: | | |
Type of mounting | | front mounting |
| | Yes |
- front mounting with central fixation
| | No |
- front mounting with 4-hole fixation
| | Yes |
| | Yes |
| | No |
Width | mm | 90 |
Height | mm | 106 |
Depth | mm | 110.5 |
Connection type: |
Design of the electrical connection / fo main current circuit | | connection terminals |
Design of the electrical connection / fo auxiliary contact | | connection terminals |
Type of the connectable conducto cross-section / fo main contacts | | |
| | 2.5 to 35 mm2 |
- finely stranded / with conducto end processing
| | 16 mm² |
| | 2.5 to 35 mm2 |
Type of connectable conducto cross section / fo auxiliary contacts | | |
| | 2x (0.75 to 2.5 mm2), 1x 4 mm2 |
- finely stranded / with conducto end processing
| | 2x (0.75 to 1.5 mm2), 1x 2.5 mm2 |
| | 2x (0.75 to 2.5 mm2), 1x 4 mm2 |
Verification of suitability | | CSA / UL / CCC / GL / LRS / DNV / PRS |
Conducto cross section that can be connected / fo main contacts / solid / minimum | mm² | 2.5 |
Conducto cross section that can be connected / fo main contacts / solid / maximum | mm² | 35 |
Conducto cross section that can be connected / fo main contacts / stranded / minimum | mm² | 2.5 |
Conducto cross section that can be connected / fo main contacts / stranded / maximum | mm² | 35 |
Conducto cross-section that can be connected / fo main contacts / stranded wire / with conducto end processing / maximum | mm² | 16 |
Conducto cross section that can be connected / fo auxiliary contacts / solid / minimum | mm² | 0.75 |
Conducto cross section that can be connected / fo auxiliary contacts / solid / maximum | mm² | 4 |
Conducto cross-section that can be connected / fo auxiliary contact / stranded wire / with conducto end processing / minimum | mm² | 0.75 |
Conducto cross-section that can be connected / fo auxiliary contact / stranded wire / with conducto end processing / maximum | mm² | 2.5 |
Conducto cross section that can be connected / fo auxiliary contacts / stranded / min. | mm² | 0.75 |
Conducto cross section that can be connected / fo auxiliary contacts / stranded / max. | mm² | 4 |