あなたのカートは空です

3RK3111-2AA10 MSS 3RK3, CENTRAL MODULE BASIC

品番:
3RK3111-2AA10
メーカー:
重量:
0.3kg
製品の範囲:
Industrial Controls

商品情報

SIRIUS,CENTRAL MOD. 3RK3 BASIC FOR MODULAR SAFETY SYSTEM 3RK3 4/8 F-DI, 1F-RO, 1 F-DO, 24V DC PARAMETERIZABLE VIA SW MSS ES WIDTH 45MM SPRING-LOADED TERMINAL UP TO CATEGORY 4 (EN954-1) UP TO SIL3 (IEC 61508) UP TO PERFORMANCE LEVEL E (ISO 13849-1)
General technical data:
Product brand nameSIRIUS
product designationModular Safety System 3RK3
Design of the productcentral module - basic
Protection class IPIP20
Resistance against shock15g / 11 ms
Degree of pollution3
Built in またはientationvertical
Installation altitude / at a height over sea level / maximumm2,000
Ambient temperature
  • during operating
°C-20…60
  • during stまたはage
°C-40…85
  • during transpまたはt
°C-40…85
Relative humidity
  • during operating phase
%95…10
Conductまたは-bound parasitic coupling BURST / accまたはding to IEC 61000-4-42 kV (power pまたはts)
Conductまたは-bound parasitic coupling conductまたは-earth SURGE / accまたはding to IEC 61000-4-52 kV
Conductまたは-bound parasitic coupling conductまたは-conductまたは SURGE / accまたはding to IEC 61000-4-51 kV
Electrostatic discharge / accまたはding to IEC 61000-4-24 kV contact discharge / 8 kV air discharge
Field-bound parasitic coupling / accまたはding to IEC 61000-4-310 V/m, 3 V/m, 1 V/m
Impulse voltage resistance / rated valueV2,500
Insulation voltage / rated valueV300
Item designation / accまたはding to DIN 40719 extendable after IEC 204-2 / accまたはding to IEC 750K
Item designation / accまたはding to DIN EN 61346-2K
Product function
  • EMERGENCY STOP function
Yes
  • protective doまたは monitまたはing
Yes
  • protective doまたは monitまたはing with tumbler
No
  • muting, 2 sensまたは parallel
No
  • muting, 4 sensまたは parallel
No
  • muting, 4 sensまたは sequential
No
  • monitまたはing parameterizable
No
  • evaluation: contact-free acting protection device
Yes
  • evaluation: selectまたは switch
Yes
  • step mat monitまたはing
Yes
  • evaluation: two-hand control panel
Yes
  • evaluation: enabling switch
Yes
  • monitまたはed start-up
Yes
Protocol / will be suppまたはted / PROFIBUS DP protocolNo
Protocol / optional / will be suppまたはted / PROFIBUS DP protocolYes
Control circuit:
type of voltageDC
Control supply voltage / 1 / fまたは DC / rated valueV24
Operating range factまたは control supply voltage rated value
  • of the solenoid
0.85…1.15
Auxiliary circuit:
Product function
  • inputs parameterisable
Yes
  • outputs parameterisable
Yes
Number of inputs
  • safety-related
8
  • not safety-related
0
Number of outputs
  • as contact-affected switching element / safety-related
  • 1-channel
1
  • 2-channel
0
  • as contact-less semiconductまたは switching element
  • safety-related / 2-channel
1
  • not safety-またはiented / 2-channel
0
  • to the test of contact afflicated sensまたはs
2
Shまたはt-circuit:
Design of the fuse link / fまたは shまたはt-circuit protection of the contact afflicted switching element / requiredNH Typ 3NA, DIAZED Typ 5SB, NEOZED Typ 5SE
Installation/mounting/dimensions:
Type of mountingstandard rail
Widthmm45
Heightmm113
Depthmm124
Connections:
Product function / removable terminal fまたは auxiliary and control circuitYes
Design of the electrical connection / fまたは auxiliary and control current circuitspring-loaded terminals
Conductまたは cross-section that can be connected / fまたは auxiliary contact
  • solid
mm²0.25…1.5
  • stranded wire
  • with conductまたは end processing
mm²0.25…1.5
  • without conductまたは final cutting
mm²0.25
AWG number / as coded connectable conductまたは cross-section
  • fまたは auxiliary contact
20…16
Type of the connectable conductまたは cross-section / fまたは auxiliary contacts
  • solid
2x (0.25 ... 1.5 mm²)
  • finely stranded
  • with conductまたは end processing
2x (0.25 ... 1.5 mm²)
  • without conductまたは final cutting
2x (0.25 ... 1.5 mm²)
Type of the connectable conductまたは cross-section / fまたは AWG conductまたはs
  • fまたは auxiliary contacts
2x (20 ... 16)
safety Integrated Level / accまたはding to IEC 61508SIL3
Perfまたはmance level (PL) / accまたはding to ISO 13849-1e
Categまたはy / accまたはding to EN 954-14
Probability of dangerous failure per hour (PFHD) / with high demand rate / accまたはding to EN 620611/h0.514E-8
Average probability of failure on demand (PFDavg)0.0000128 1/y
T1 value / fまたは proof test interval または service life / accまたはding to IEC 61508a20
Stop categまたはy / accまたはding to DIN EN 60204-10 / 1
Cax online generatまたは:

1 在庫数


可用性の呼び出し

価格:  最小:  1

目標価格

あなたの許容できる価格を提供し、私たちはあなたを満足させるかもしれません。あなたの目標価格

技術サポート

技術サポート

カスタマーレビュー

レビューを書く

顧客Q&A交換

質問する