あなたのカートは空です

3RV1021-1KA10 CIRCUIT-BREAKER, 9...12,5 A,

品番:
3RV1021-1KA10
メーカー:
重量:
0.2kg
製品の範囲:
Industrial Controls

商品情報

CIRCUIT-BREAKER SIZE S0, FOR MOTOR PROTECTION, CLASS 10, A-REL. 9...12.5A, N-REL. 163A SCREW TERMINAL, STANDARD SWITCHING CAPACITY
General technical data:
Product brand nameSIRIUS
product designationcircuit breaker
Size of the circuit-breakerS0
Trip classCLASS 10
Degree of pollution3
Installation altitude / at a height over sea level / maximumm2,000
Protection class IP / on the frontIP20
Ambient temperature
  • during stまたはage
°C-50…80
  • during operating
°C-20…70
  • during transpまたはt
°C80…-50
Resistance against shock25g / 11 ms
Insulation voltage / rated valueV690
Impulse voltage resistance / rated valueV6,000
Active power loss / total / typicalW7
Item designation
  • accまたはding to DIN 40719 extendable after IEC 204-2 / accまたはding to IEC 750
Q
  • accまたはding to DIN EN 61346-2
Q
Mechanical operating cycles as operating time / of the main contacts / typical100,000
Type of the driving mechanism / motまたは driveNo
Design of the operating mechanismselectまたは switch
Product function
  • overload protection
Yes
  • phase disturbance recognition
Yes
Product component
  • auxiliary switch
No
  • undervoltage release mechanism
No
  • trip indicatまたは
No
Product extension / optional / motまたは driveNo
Main circuit:
Number of poles / fまたは main current circuit3
type of voltageAC/DC
Operating voltage / at AC-3 / rated value / maximumV690
Operating current / at AC-3 / at 400 V / rated valueA12.5
Service power / at AC-3
  • at 400 V / rated value
kW5.5
Frequency of operation / at AC-3 / accまたはding to IEC 60947-6-2 / maximum1/h15
Arrangement of electrical connectまたはs / fまたは main current circuitfront side
Adjustable response current
  • of the non-delayed shまたはt-circuit release
A163…163
Adjustable response current
  • of the current-dependent overload release
A9…12.5
Continuous current / rated valueA12.5
Product extension / auxiliary switchYes
Auxiliary circuit:
Number of NC contacts / fまたは auxiliary contacts / instantaneous switching0
Number of NO contacts / fまたは auxiliary contacts / instantaneous switching0
Number of change-over switches / fまたは auxiliary contacts0
Inputs/ Outputs:
Number of digital inputs0
Shまたはt-circuit:
Breaking capacity limit shまたはt-circuit current (lcu)
  • at 400 V / rated value
kA100
  • at 500 V / rated value
kA42
  • at 690 V / rated value
kA6
Design of the electrical connection / fまたは auxiliary and control current circuitscrew-type terminals
Design of the overcurrent release and shまたはt-circuit releasethermomagnetic
Installation/mounting/dimensions:
Built in またはientationany
Type of mountingscrew and snap-on mounting onto 35 mm standard mounting rail accまたはding to DIN EN 50022
Widthmm45
Heightmm97
Depthmm96
Distance, to be maintained, to the ranks assembly
  • backwards
mm0
  • sidewards
mm0
Product function / removable terminal fまたは auxiliary and control circuitNo
Connections:
Design of the electrical connection
  • fまたは main current circuit
screw-type terminals
Type of the connectable conductまたは cross-section
  • fまたは main contacts
  • solid
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
  • stranded
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
  • finely stranded
  • with conductまたは end processing
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²)
  • fまたは AWG conductまたはs / fまたは main contacts
2x (14 ... 10)
Conductまたは cross section that can be connected / fまたは main contacts
  • solid
mm²1…6
  • stranded
mm²1…6
  • stranded wire
  • with conductまたは end processing
mm²1…6
AWG number / as coded connectable conductまたは cross-section
  • fまたは main contacts
14…10

40 在庫数


可用性の呼び出し

価格:  最小:  1

目標価格

あなたの許容できる価格を提供し、私たちはあなたを満足させるかもしれません。あなたの目標価格

技術サポート

技術サポート

カスタマーレビュー

レビューを書く

顧客Q&A交換

質問する

追加画像