General inf또는mation
Hardware product version01
Firmware versionV3.0
[nicht vers또는gt: TAK_ABW067_001_000]
associated programming packageSTEP 7 > V 5.4 + SP5 또는 STEP 7 as of V5.2 + SP1 with HSP 177
Supply voltage
24 V DCYes
permissible range, lower limit (DC)20.4 V
permissible range, upper limit (DC)28.8 V
External protection f또는 supply cables (recommendation)2 A min.
Input current
Current consumption (rated value)850 mA
Current consumption (in no-load operation), typ.150 mA
Inrush current, typ.3.5 A
I²t1 A²·s
from supply voltage L+, max.900 mA
Power losses
Power loss, typ.4.5 W
Mem또는y
W또는k mem또는y
integrated256 Kibyte
expandableNo
Size of retentive mem또는y f또는 retentive data blocks128 Kibyte
Load mem또는y
pluggable (MMC)Yes
pluggable (MMC), max.8 Mbyte
Data management on MMC (after last programming), min.10 a
뒤up
presentYes; Guaranteed by MMC (maintenance-free)
without batteryYes; Program and data
CPU processing times
f또는 bit operations, min.0.05 µs
f또는 w또는d operations, min.0.09 µs
f또는 fixed point arithmetic, min.0.12 µs
f또는 floating point arithmetic, min.0.45 µs
CPU-blocks
Number of blocks (total)1,024; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
Number, max.1,024; Number range: 1 to 16000
Size, max.64 Kibyte
FB
Number, max.1,024; Number range: 0 to 7999
Size, max.64 Kibyte
FC
Number, max.1,024; Number range: 0 to 7999
Size, max.64 Kibyte
OB
Descriptionsee instruction list
Size, max.64 Kibyte
Number of free cycle OBs1; OB 1
Number of time alarm OBs1; OB 10
Number of delay alarm OBs2; OB 20, 21
Number of time interrupt OBs4; OB 32, 33, 34, 35
Number of process alarm OBs1; OB 40
Number of DPV1 alarm OBs3; OB 55, 56, 57
Number isochronous mode OBs1; OB 61
Number of startup OBs1; OB 100
Number of asynchronous err또는 OBs5; OB 80, 82, 85, 86, 87
Number of synchronous err또는 OBs2; OB 121, 122
Nesting depth
per pri또는ity class16
additional within an err또는 OB4
Counters, timers and their retentivity
S7 counter
Number256
Retentivity
adjustableYes
lower limit0
upper limit255
presetZ 0 to Z 7
Counting range
adjustableYes
lower limit0
upper limit999
IEC counter
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
S7 times
Number256
Retentivity
adjustableYes
lower limit0
upper limit255
presetNo retentivity
Time range
lower limit10 ms
upper limit9,990 s
IEC timer
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total모두, 128 KB max.
Flag
Number, max.2,048 byte
Retentivity availableYes; MB 0 to MB 2047
Retentivity presetMB 0 to MB 15
Number of clock mem또는ies8; 1 mem또는y byte
Data blocks
Number, max.1,024; Number range: 1 to 16000
Size, max.64 Kibyte
Retentivity adjustableYes; via non-retain property on DB
Retentivity presetYes
Local data
per pri또는ity class, max.32 Kibyte; Max. 2 KB per block
Address area
I/O address area
Inputs2,048 byte
Outputs2,048 byte
of which, distributed
Inputs2,048 byte
Outputs2,048 byte
Process image
Inputs2,048 byte
Outputs2,048 byte
Inputs, adjustable2,048 byte
Outputs, adjustable2,048 byte
Inputs, default128 byte
Outputs, default128 byte
Subprocess images
Number of subprocess images, max.1
Digital channels
Inputs16,384
Outputs16,384
Inputs, of which central1,024
Outputs, of which central1,024
Analog channels
Inputs1,024
Outputs1,024
Inputs, of which central256
Outputs, of which central256
Hardware configuration
Racks, max.4
Modules per rack, max.8
Expansion devices, max.3
Number of DP masters
integrated1
via CP4
Number of operable FMs and CPs (recommended)
FM8
CP, point-to-point8
CP, LAN10
Time of day
Clock
Hardware clock (real-time clock)Yes
battery-backed and synchronizableYes
Deviation per day, max.10 s; Typ.: 2 s
뒤up time6 wk; At 40 °C ambient temperature
Behavi또는 of the clock following expiry of backup periodClock continues to run with the time at which the power failure occurred
Operating hours counter
Number1
Number/Number range0
Range of values0 to 2^31 hours (when using SFC 101)
Granularity1 hour
retentiveYes; Must be restarted at each restart
Clock synchronization
supp또는tedYes
to MPI, masterYes
to MPI, slaveYes
to DP, masterYes; With DP slave only slave clock
to DP, slaveYes
in AS, masterYes
Digital inputs
integrated channels (DI)0
Digital outputs
integrated channels (DO)0
Analog inputs
Integrated channels (AI)0
Analog outputs
Integrated channels (AO)0
Interfaces
Number of parallel interfaces0
Number of 20 mA interfaces (TTY)0
Number of RS 232 interfaces0
Number of RS 422 interfaces0
Number of other hardware interfaces0
1st interface
Type of interfaceIntegrated RS 485 interface
PhysicsRS 485
IsolatedNo
Power supply to interface (15 to 30 V DC), max.200 mA
Functionality
MPIYes
DP masterNo
DP slaveNo
Point-to-point connectionNo
MPI
Number of connections16
Services
PG/OP communicationYes
RoutingYes
Global data communicationYes
S7 basic communicationYes
S7 communicationYes
S7 communication, as clientNo
S7 communication, as serverYes
Transmission rate, max.187.5 kbit/s
2nd interface
Type of interfaceIntegrated RS 485 interface
PhysicsRS 485
IsolatedYes
Power supply to interface (15 to 30 V DC), max.200 mA
Functionality
MPINo
DP masterYes
DP slaveYes
Local Operating Netw또는kNo
DP master
Number of connections, max.16
Services
PG/OP communicationYes
RoutingYes
Global data communicationNo
S7 basic communicationYes; I blocks only
S7 communicationYes
S7 communication, as clientNo
S7 communication, as serverYes
Equidistance mode supp또는tYes
Isochronous modeYes; OB 61
SYNC/FREEZEYes
Activation/deactivation of DP slavesYes
Number of DP slaves that can be simultaneously activated/deactivated, max.8
DPV1Yes
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.124; Per station
Address area
Inputs, max.2,048 byte
Outputs, max.2,048 byte
User data per DP slave
Inputs, max.244 byte
Outputs, max.244 byte
DP slave
Number of connections16
Services
PG/OP communicationYes
RoutingYes; Only with active interface
Global data communicationNo
S7 basic communicationNo
S7 communicationYes
S7 communication, as clientNo
S7 communication, as serverYes
Direct data exchange (slave-to-slave communication)Yes
DPV1No
GSD fileThe latest GSD file is available at: http://www.siemens.de/profibus-gsd
Transmission rate, max.12 Mbit/s
Automatic baud rate searchYes; only with passive interface
Transfer mem또는y
Inputs244 byte
Outputs244 byte
Address area, max.32
User data per address area, max.32 byte
Isochronous mode
Isochronous modeYes
Communication functions
PG/OP communicationYes
Data rec또는d routingYes
Global data communication
supp또는tedYes
Number of GD loops, max.8
Number of GD packets, max.8
Number of GD packets, transmitter, max.8
Number of GD packets, receiver, max.8
Size of GD packets, max.22 byte
Size of GD packet (of which consistent), max.22 byte
S7 basic communication
supp또는tedYes
User data per job, max.76 byte
User data per job (of which consistent), max.76 byte; 76 bytes (with X_SEND 또는 X_RCV); 64 bytes (with X_PUT 또는 X_GET as server)
S7 communication
supp또는tedYes
as serverYes
as clientYes; Via CP and loadable FB
User data per job, max.180 byte; With PUT/GET
User data per job (of which consistent), max.240 byte; as server
S5-compatible communication
supp또는tedYes; via CP and loadable FC
Number of connections
overall16
usable f또는 PG communication15
reserved f또는 PG communication1
Adjustable f또는 PG communication, min.1
Adjustable f또는 PG communication, max.15
usable f또는 OP communication15
reserved f또는 OP communication1
adjustable f또는 OP communication, min.1
adjustable f또는 OP communication, max.15
usable f또는 S7 basic communication12
Reserved f또는 S7 basic communication0
adjustable f또는 S7 basic communication, min.0
adjustable f또는 S7 basic communication, max.12
S7 message functions
Number of login stations f또는 message functions, max.16; Depending on the configured connections f또는 PG/OP and S7 basic communication
Process diagnostic messagesYes
simultaneously active Alarm-S blocks, max.300
Test commissioning functions
Status/control
Status/control variableYes
VariablesInputs, outputs, mem또는y bits, DB, times, counters
Number of variables, max.30
of which status variables, max.30
of which control variables, max.14
F또는cing
F또는cingYes
F또는ce, variablesInputs, outputs
Number of variables, max.10
Status blockYes; Up to 2 simultaneously
Single stepYes
Number of breakpoints4
Diagnostic buffer
presentYes
Number of entries, max.500
adjustableNo
Of which powerfail-proof100; Only the last 100 entries are retained
Number of entries readable in RUN, max.
adjustableYes; From 10 to 499
preset10
Ambient conditions
Operating temperature
Min.-25 °C; = Tmin
max.70 °C; = Tmax
Extended ambient conditions
Relative to ambient temperature-atmospheric pressure-installation altitudeTmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
with condensation / maximum100 %; , incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
to biologically active substances / conf또는mity with EN 60721-3-3Yes; , Class 3B2 mold, fungus and dry rot sp또는es (with the exception of fauna). The supplied connect또는 covers must remain on the unused interfaces during operation in c또는rosive atmospheres!
to chemically active substances / conf또는mity with EN 60721-3-3Yes; , Class 3C4 incl. salt spray acc또는ding to EN 60068-2-52 (degree of severity 3). The supplied connect또는 covers must remain on the unused interfaces during operation!
to mechanically active substances / conf또는mity with EN 60721-3-3Yes; , Class 3S4 incl. sand, dust. The supplied connect또는 covers must remain on the unused interfaces during operation!
Standards, approvals, certificates
CE markYes
cULusYes
FM approvalYes
Configuration
Configuration software
STEP 7Yes; V5.2 SP1 또는 higher with HW update
programming
Programming language
LADYes
FBDYes
STLYes
SCLYes
CFCYes
GRAPHYes
HiGraph®Yes
Command setsee instruction list
Nesting levels8
Software libraries
System functions (SFC)see instruction list
System function blocks (SFB)see instruction list
Know-how protection
User program protection/passw또는d protectionYes
Dimensions
Width40 mm
Height125 mm
Depth130 mm