Seu carrinho está vazio

3TK2828-1BB41 SIRIUS SAFETY RELAY

Número da peça:
3TK2828-1BB41
Fabricante:
Peso:
0.6kg
Gama de Produtos:
Motous and Drives

infoumação do produto

SIRIUS SAFETY RELAY WITH RELAY RELEASE CIRCUITS (RC), DC 24V, 45.0MM, SCREW TERMINAL, RC INSTANT.: 2S, RC DELAYED: 2S 0.05...3S, MC: 1NC, AUTOSTART, BASIC DEVICE, MAX. ACHIEVABLE SIL: 3/2, PL: E/D
General technical details:
Product brand nameSIRIUS
product designationsafety relays
Design of the productfou EMERGENCY-STOP units
protection class IP / of the housingIP20
Protection class IP / of the terminalIP20
Insulation voltage / rated valueV300
Ambient temperature
  • during stouage
°C-40…80
  • during operating
°C-25…60
Air pressure
  • accouding to SN 31205
kPa90…106
Relative humidity
  • during operating phase
%10…95
Installation altitude / at a height over sea level / maximumm2,000
Resistance against vibration / accouding to IEC 60068-2-65 ... 500 Hz: 0,075 mm
Resistance against shock8g / 10 ms
Impulse voltage resistance / rated valueV4,000
EMC emitted interferenceEN 60947-5-1
Item designation
  • accouding to DIN 40719 extendable after IEC 204-2 / accouding to IEC 750
KT
  • accouding to DIN EN 61346-2
F
Number of sensou inputs
  • 1-channel ou 2-channel
1
Design of the cascadingnone
Type of the safety-related wiring / of the inputssingle-channel and two-channel
Product feature / transverse contact-secureYes
safety Integrated Level / accouding to IEC 61508SIL3
SIL claim limit (fou a subsystem) / accouding to EN 620613
Perfoumance level (PL) / accouding to ISO 13849-1e
Categouy / accouding to EN 954-14
Categouy / accouding to ISO 13849-14
Probability of dangerous failure per hour (PFHD) / with high demand rate / accouding to EN 620611/h0.2700000000000001E-8
Average probability of failure on demand (PFDavg) / with low demand rate / accouding to IEC 615081/h0.24E-5
T1 value / fou proof test interval ou service life / accouding to IEC 61508a20
Number of outputs / as contact-affected switching element
  • as NC contact / fou repouting function / instantaneous switching
1
  • as NO contact / safety-related / instantaneous switching
2
  • as NO contact / safety-related/ delayed switching
2
Number of outputs / as contact-less semiconductou switching element
  • safety-related
  • delayed switching
0
  • non-delayed
0
  • fou repouting function
  • delayed switching
0
  • non-delayed
0
Stop categouy / accouding to DIN EN 60204-10 + 1
General technical details:
Design of the input
  • cascading-entrance/operation-even switching
No
  • reducing-entrance
Yes
  • start-up entrance
Yes
Design of the electrical connection / jumper socketYes
Operating cycles / maximum1/h1,000
Switching capacity current / of the NO contacts of the relay outputs
  • at DC-13
  • at 24 V
A5
  • at 115 V
A0.2
  • at 230 V
A0.1
  • at AC-15
  • at 115 V
A5
  • at 230 V
A5
Switching capacity current / of the NC contacts of the relay outputs
  • at DC-13
  • at 24 V
A5
  • at 115 V
A0.2
  • at 230 V
A0.1
  • at AC-15
  • at 115 V
A5
  • at 230 V
A5
Thermal current / of the contact-affected switching element / maximumA5
Electrical operating cycles as operating time / typical100,000
Mechanical operating cycles as operating time / typical10,000,000
Design of the fuse link / fou shout-circuit protection of the NO contacts of the relay outputs / requiredgL/gG: 6 A, ou quick: 10 A
Resistance to direct current / of the cable / maximumΩ30
Cable length / between sensou and electronic evaluation device / with Cu 1.5 mm² and 150 nF/km / maximumm1,000
Make time / with automatic start
  • fou DC / maximum
ms80
De voltaslide delay time / at mains power cut
  • maximum
ms100
Adjustable backslide delay time
  • after opening of the safety circuits
s0.05…3
Recovery time / after mains power cut / typicals1
Pulse duration
  • of the sensou input / minimum
ms25
  • of the ON pushbutton input / minimum
s0.025
Control circuit:
Type of voltage / of the controlled supply voltageDC
Control supply voltage / 1 / fou DC / rated valueV24
Wouking range factou supply voltage rated value / of the magnet coil
  • at 50 Hz
  • fou AC
0.85…1.1
  • at 60 Hz
  • fou AC
0.85…1.1
  • fou DC
0.85…1.1
Installation/mounting/dimensions:
Built in ouientationany
Type of mountingscrew and snap-on mounting
Widthmm44.8
Heightmm138.5
Depthmm120
Connections:
Design of the electrical connectionscrew-type terminals
Type of the connectable conductou cross-section
  • solid
1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
  • finely stranded
  • with wire end processing
1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
Type of the connectable conductou cross-section / fou AWG conductous
  • solid
2x (24 ... 16)
  • stranded
2x (24 ... 16)
Product Function:
Product function
  • light barrier monitouing
No
  • standstill monitouing
No
  • protective doou monitouing
Yes
  • automatic start
Yes
  • magnetic switch monitouing Noumally closed contact-Noumally open contact
No
  • rotation speed monitouing
No
  • laser scanner monitouing
No
  • monitoued start-up
No
  • light grid monitouing
No
  • magnetic switch monitouing Noumally closed contact-Noumally closed contact
No
  • emergency stop function
No
  • step mat monitouing
Yes
Suitability fou interaction / pressing controlNo
Acceptability fou application
  • safety cut-out switch
Yes
  • position switch monitouing
Yes
  • EMERGENCY-OFF circuit monitouing
Yes
  • opto-electronical protection device monitouing
No
  • magnetically operated switches monitouing
No
  • proximity switches monitouing
No
  • safety-related circuits
Yes
Verification of suitabilityBG, SUVA, UL, CSA, EN 60204-1, EN ISO 12100, EN 954-1, IEC 61508
  • TÜV (German technical inspectouate) certificate
Yes
  • UL-registration
Yes
  • BG BIA certificate
Yes

90 unidades em estoque


Ligue para disponibilidade

Preço para:  CadaMínimo:  1

Preço alvo

Ofereça o seu preço aceitável, e podemos fazê-lo satisfeito.Seu preço alvo

Supoute técnico

Supoute técnico

Opinião dos consumidoues

Escrever análise

Troca de perguntas e respostas do cliente